| 參數(shù) | 描述 | P | TPY | 計(jì)量 | PR | PX | TPS | TPX | TPZ | 
| 額定一次電流 | 用于計(jì)算準(zhǔn)確的實(shí)際電流比 | √ | √ | √ | √ | √ | √ | √ | √ | 
額定負(fù)荷, 功率因數(shù) | 銘牌上的額定負(fù)荷,功率因數(shù)為0.8或1 | √ | √ | √ | √ | √ | √ | √ | √ | 
|   |   | √ | √ | √ | √ | √ | √ | √ | √ | 
| 額定準(zhǔn)確限值系數(shù) | 銘牌上的規(guī)定,默認(rèn):10。用于計(jì)算極限電動(dòng)勢及其對應(yīng)的復(fù)合誤差 | √ |   |   |   |   |   |   |   | 
| 額定對稱短路電流系數(shù) | 銘牌上的規(guī)定,默認(rèn):10。用于計(jì)算極限電動(dòng)勢及其對應(yīng)的峰瞬誤差 |   | √ |   |   |   | √ | √ | √ | 
| 一次時(shí)間常數(shù) | 默認(rèn):100ms |   | √ |   |   |   |   | √ | √ | 
| 二次時(shí)間常數(shù) | 默認(rèn):3000ms |   | √ |   |   |   |   |   | √ | 
| 工作循環(huán) | C-t1-O或C-t1-O-tfr-C-t2-O,默認(rèn):C-t1-O循環(huán) |   | √ |   |   |   |   | √ |   | 
| t1 | *次電流通過時(shí)間,默認(rèn):100ms |   | √ |   |   |   |   | √ |   | 
| tal1 | 一次通流保持準(zhǔn)確限值的時(shí)間,默認(rèn):40ms |   |   |   |   |   |   |   |   | 
| tfr | *次打開和重合閘的延時(shí),默認(rèn):500ms。選擇C-t1-O-tfr-C-t2-O循環(huán)才顯示 |   | √ |   |   |   |   | √ |   | 
| t2 | 第二次電流通過時(shí)間,默認(rèn):100ms。選擇C-t1-O-tfr-C-t2-O循環(huán)才顯示 |   | √ |   | √ |   |   | √ |   | 
| tal2 | 二次通流保持準(zhǔn)確限值的時(shí)間,默認(rèn):40ms 選擇C-t1-O-tfr-C-t2-O循環(huán)才顯示 |   | √ |   |   |   |   | √ |   | 
| 額定儀表保安系數(shù) | 銘牌上的規(guī)定,默認(rèn)值:10。 用于計(jì)算極限電動(dòng)勢及其對應(yīng)的復(fù)合誤差 |   |   | √ |   |   |   |   |   | 
| 額定計(jì)算系數(shù) |   |   |   |   |   | √ |   |   |   | 
| 額定拐點(diǎn)電勢Ek |   |   |   |   |   | √ |   |   |   | 
| Ek對應(yīng)的Ie |   |   |   |   |   | √ |   |   |   | 
| 面積系數(shù) |   |   |   |   |   |   | √ |   |   | 
| 額定Ual | 額定等效二次極限電壓 |   |   |   |   |   | √ |   |   | 
| Ual對應(yīng)的Ial |   |